3.—(1) For the purpose of section 64(1)(a) of the Act, the minimum electrical load in respect of a development on which building works are carried out is determined in accordance with the formula 1.3 kVA × TPL, where TPL is the total number of parking lots in the parking places of the development.| (2) For the purpose of section 64(1)(b) of the Act, the minimum number of charging points in the parking places of the development is the number of charging points (called N) that draws the aggregate amount of electrical load (as measured in kilowatts) determined in accordance with the formula prescribed by sub‑paragraph (3) and, if N is not a whole number, rounding that number to the next higher whole number. |
(3) In sub‑paragraph (2), the formula to determine the aggregate amount of electrical load (as measured in kilowatts) is 0.2 × (MEL × PF), where —| (a) | MEL is the minimum electrical load prescribed by sub‑paragraph (1); and | | (b) | PF is the power factor of 0.85. |
|
|