PART 2B MINIMUM ENERGY EFFICIENCY STANDARDS FOR ENERGY-CONSUMING SYSTEMS |
[S 972/2020 wef 01/12/2020] [S 719/2025 wef 31/12/2021] 7F. In this Part, unless the context otherwise requires —| “antifreeze” means any additive that prevents water from freezing by depressing the freezing point of water; |
| “assessment report” means a report mentioned in section 26B(2)(b)(i) or (3)(b) of the Act; [S 719/2025 wef 01/12/2025] |
| “booster pump” means a pump that is installed on a chilled water pipeline to overcome a drop in pressure in the chilled water pipeline, to prevent over-pressurising chilled water in any parallel pipeline; |
| “building” has the meaning given by section 2 of the Planning Act 1998; [S 719/2025 wef 01/12/2025] |
| “certificate of statutory completion” has the meaning given by section 2(1) of the Building Control Act 1989; [S 619/2022 wef 31/12/2021] |
| “cooling tower” means any device in which atmospheric air is passed through sprayed water to lower the temperature of the sprayed water by evaporative cooling; |
| “development” has the meaning given by section 3 of the Planning Act 1998; [S 719/2025 wef 01/12/2025] |
“end-to-end uncertainty”, in relation to a parameter of a prescribed system, means the combined uncertainty of —| (a) | every prescribed measuring instrument installed for the prescribed system for measuring that parameter; and [S 719/2025 wef 01/12/2025] | | (b) | any accessory needed for the operation of those prescribed measuring instruments, including a current or voltage transformer; [S 719/2025 wef 01/12/2025] |
|
| “energy management system”, in relation to a prescribed system, means a system that processes, analyses, displays and stores data collected from prescribed measuring instruments installed for the prescribed system; [S 719/2025 wef 01/12/2025] |
“energy performance”, in relation to a prescribed system, means —| (a) | the ratio of electrical power consumption (measured in kilowatts) to the refrigeration output (measured in kilowatts) of the prescribed system; or | | (b) | the ratio of electrical energy consumption (measured in kilowatt-hours) to the refrigeration energy output (measured in kilowatt-hours) of the prescribed system; |
|
| “gross floor area” has the same meaning as “floor area” in rule 2 of the Planning (Development) Rules 2008 (G.N. No. S 113/2008); [S 619/2022 wef 01/08/2022] |
| “kWc”, in relation to a prescribed system, means the refrigeration output of the prescribed system, expressed in kilowatts; |
| “monitoring report” means a report mentioned in section 26B(2)(b)(ii) of the Act; [S 719/2025 wef 01/12/2025] |
“new building” means a building or part of a building —| (a) | that is developed (other than by way of retrofitting) in either of the following circumstances:| (i) | where an application for planning permission for the development was or is submitted on or after 1 December 2020 under the Planning Act 1998; | | (ii) | where the Minister charged with the responsibility for national development has authorised or authorises, on or after 1 December 2020 under section 21(6) of the Planning Act 1998, the carrying out of the development subject to a condition that plans of the development must be lodged with the competent authority before the development commences; and |
| | (b) | which is served by a prescribed system that serves only the building or part of the building; [S 719/2025 wef 01/12/2025] |
|
| [Deleted by S 719/2025 wef 01/12/2025] |
| “prescribed measuring instrument” means a measuring instrument mentioned in regulation 7J(1); [S 719/2025 wef 01/12/2025] |
| “prescribed system” means an energy-consuming system mentioned in regulation 7H; |
“qualified person” means —| (a) | an individual who is certified by the Institution of Engineers, Singapore as an energy efficiency opportunities assessor with systems-specific experience in chilled water systems; or | | (b) | a professional engineer registered under the Professional Engineers Act 1991 in the branch of mechanical engineering, electrical engineering or chemical engineering, who has in force a practising certificate issued under that Act; [S 619/2022 wef 31/12/2021] |
|
| “retrofit” has the meaning given by section 2(1) of the Building Control Act 1989; [S 719/2025 wef 01/12/2025] |
| “specified AHRI Standard” means the AHRI Standard 551/591-SI-2018 published by the Air-Conditioning, Heating and Refrigeration Institute; |
| “SS 591/2013” means the Singapore Standard 591:2013 — Code of Practice for long term measurement of central chilled water system energy efficiency, published by the Enterprise Singapore Board; |
| “temporary occupation permit” has the meaning given by section 2(1) of the Building Control Act 1989; [S 619/2022 wef 31/12/2021] |
“water-cooled chilled water system” means a system comprising one or more of each of the following components:| (a) | a water-cooled chiller; | | (b) | a chilled water pump for a water-cooled chiller; | | (c) | a condenser water pump; | | (d) | a cooling tower, |
| with interconnections and accessories (including thermal storage tanks, if any), operating together to produce chilled water, whether or not each component is situated in the same premises, and excludes any booster pump and other energy-consuming systems that use the chilled water produced, either directly or indirectly; |
|
“water-cooled chiller” means a factory-made and prefabricated assembly (whether or not it is shipped as one package) comprising one or more of each of the following:| (a) | a compressor; | | (b) | a water-cooled condenser; | | (c) | an evaporator, |
| with interconnections and accessories, designed to produce chilled water by using a vapour compression refrigeration cycle to remove heat from chilled water in the evaporator and reject the heat to water in the condenser; |
|
| “water-cooled condenser” means a refrigeration system component where refrigerant vapour is condensed and the heat rejected to water, resulting in a rise in water temperature. [S 972/2020 wef 01/12/2020] |
|
7G. Section 26B(1) of the Act applies to a corporation that has operational control of —| (a) | any premises that are located within any land that is zoned as a Business 1 or Business 2 zone in the Master Plan under the Planning Act 1998; or [S 619/2022 wef 31/12/2021] | | (b) | a business activity that is attributable to any of the following industry sectors:| (i) | manufacturing and manufacturing-related services; | | (ii) | supply of electricity, gas, steam, compressed air and chilled water for air-conditioning; | | (iii) | water supply and sewage and waste management. [S 972/2020 wef 01/12/2020] |
|
|
| Prescribed energy-consuming system |
7H. For the purposes of section 26B(2) of the Act, the prescribed energy-consuming system is a water-cooled chilled water system that —| (a) | is electrically driven; | | (b) | comprises at least one chiller that produces, or the registered relevant person intends to be used to produce, chilled water without requiring the use of antifreeze; [S 719/2025 wef 01/12/2025] | | (c) | has a total refrigeration capacity of 1055 kWc or more when rated —| (i) | at standard rating conditions in accordance with the specified AHRI Standard; or | | (ii) | in accordance with the operational conditions required for the business activity; and [S 719/2025 wef 01/12/2025] |
| | (d) | generates, or the registered relevant person intends to be used to generate, chilled water at a temperature of 3°C or higher, |
| but excludes any chiller or part of a chiller comprised in the water-cooled chilled water system that produces, or that the registered relevant person intends to be used for the production of, chilled water requiring the use of antifreeze, and any chilled water pump for that chiller or part and interconnections to the pump. |
[S 972/2020 wef 01/12/2020] [S 719/2025 wef 01/12/2025] |
| 7I. [Deleted by S 719/2025 wef 01/12/2025] |
| Prescribed measuring instruments |
7J.—(1) For the purposes of section 26B(2) of the Act, the following are the prescribed measuring instruments for the purpose of assessing the energy efficiency of a prescribed system:| (a) | subject to paragraph (2) —| (i) | a permanent temperature sensor to measure the chilled water supply temperature of each water-cooled chiller in the prescribed system; and [S 719/2025 wef 01/12/2025] | | (ii) | a permanent temperature sensor to measure the chilled water return temperature of each water-cooled chiller in the prescribed system; [S 719/2025 wef 01/12/2025] |
| | (b) | subject to paragraphs (2) and (4), a permanent temperature sensor to measure the condenser water supply temperature of each water-cooled chiller in the prescribed system; [S 719/2025 wef 01/12/2025] | | (c) | subject to paragraphs (2) and (4), a permanent temperature sensor to measure the condenser water return temperature of each water-cooled chiller in the prescribed system; [S 719/2025 wef 01/12/2025] | | (d) | subject to paragraph (2), one or more permanent flowmeters by or from which the flowrate of the chilled water in each water-cooled chiller in the prescribed system may be measured or derived; [S 719/2025 wef 01/12/2025] | | (e) | subject to paragraphs (2) and (4), one or more permanent flowmeters by or from which the flowrate of the condenser water in each water-cooled chiller in the prescribed system may be measured or derived; [S 719/2025 wef 01/12/2025] | | (f) | one or more permanent power meters by which the total electrical energy and electrical power consumption of each of the following groups of equipment may be measured or derived:| (i) | the water-cooled chillers; | | (ii) | the chilled water pumps; | | (iii) | the condenser water pumps; | | (iv) | the cooling towers. [S 719/2025 wef 01/12/2025] |
|
(2) Where water-cooled chillers share a common chilled water header or a common condenser water header —| (a) | a permanent temperature sensor may be installed at the common header for the chilled water or the condenser water, as the case may be —| (i) | instead of for each water-cooled chiller; or | | (ii) | in addition to the permanent temperature sensors for each water-cooled chiller; and [S 719/2025 wef 01/12/2025] |
| | (b) | if permanent temperature sensors are installed at the common headers to measure both the water supply and return temperatures for the chilled water or condenser water, a permanent flowmeter may be installed at any common header for the chilled water or condenser water, as the case may be —| (i) | instead of for each water-cooled chiller; or | | (ii) | in addition to the permanent flowmeters for each water-cooled chiller. [S 719/2025 wef 01/12/2025] |
|
|
(3) In relation to each permanent temperature sensor mentioned in paragraph (1)(a), (b) or (c) —| (a) | a test plug or thermowell, with an open tip slightly larger than a diameter of 3.2 mm, must also be installed on the chilled water and condenser pipelines —| (i) | before and after each permanent temperature sensor; and | | (ii) | at easily accessible locations, where possible; and |
| | (b) | any thermowell installed must enable the permanent temperature sensor inserted in the thermowell to come into direct contact with the fluid in the pipeline. [S 719/2025 wef 01/12/2025] |
|
| (4) Paragraph (1)(b), (c) and (e) does not apply if the amount or rate of heat rejection of the prescribed system may be derived from other temperature and flowrate measurements taken in the prescribed system. |
(5) The end-to-end uncertainty for each measurement from a prescribed measuring instrument must not exceed —| (a) | for a permanent temperature sensor — ±0.05°C; [S 719/2025 wef 01/12/2025] | | (b) | for a permanent flowmeter — ±1%; and [S 719/2025 wef 01/12/2025] | | (c) | for a permanent power meter — ±2%. [S 719/2025 wef 01/12/2025] |
|
| (6) Where a registered relevant person satisfies the Director-General that it is not reasonably practicable to install a permanent flowmeter that complies with paragraph (5)(b), the registered relevant person may install a permanent flowmeter with an uncertainty for each measurement that does not exceed ±2%. [S 719/2025 wef 01/12/2025] |
| (7) The overall end-to-end uncertainty of all the prescribed measuring instruments used in the prescribed system must not exceed ±5%. [S 719/2025 wef 01/12/2025] |
(8) For the purposes of paragraph (7), the overall end-to-end uncertainty of the prescribed measuring instruments is the number ascertained by calculating the square root of the formula A2 + B2 + C2, where —| (a) | A is the percentage end-to-end uncertainty of the difference between the chilled water supply and return temperatures, calculated in accordance with the formula where —| (i) | D is the end-to-end uncertainty of the chilled water supply temperature measurement; | | (ii) | E is the end-to-end uncertainty of the chilled water return temperature measurement; and | | (iii) | F is the smallest value of all values calculated for the prescribed system of the measured chilled water return temperatures less the measured chilled water supply temperatures for the water-cooled chillers in the prescribed system; |
| | (b) | B is the percentage end-to-end uncertainty of the chilled water flowrate measurement; and | | (c) | C is the percentage end-to-end uncertainty of power consumption measurement. [S 719/2025 wef 01/12/2025] |
|
| (9) The percentage system heat balance for the prescribed system (calculated in accordance with paragraph B.2.2 of SS 591/2013) must be within ±5% for at least 80% of data points. [S 972/2020 wef 01/12/2020] [S 719/2025 wef 01/12/2025] |
|
| Prescribed manner of assessment |
7K.—(1) The assessment of the energy efficiency of a prescribed system must be carried out in the following manner:| (a) | the assessment must be based on measurements made by the prescribed measuring instruments —| (i) | collected at intervals of one minute and recorded in 3 decimal places or more; | | (ii) | collected from the operation of the prescribed system over a continuous period of not less than 2 weeks (called in these Regulations the assessment period); and | | (iii) | stored in an energy management system that stores and calculates the information specified in paragraph (3); [S 719/2025 wef 01/12/2025] |
| | (b) | a qualified person must certify that regulation 7J is complied with in relation to every prescribed measuring instrument installed for the prescribed system and that the energy management system mentioned in sub-paragraph (a)(iii) accurately calculates the information specified in paragraph (3); [S 719/2025 wef 01/12/2025] | | (c) | the qualified person mentioned in sub-paragraph (b) must separately verify the energy efficiency of the prescribed system calculated by the energy management system, using the measurements mentioned in sub-paragraph (a). [S 719/2025 wef 01/12/2025] |
| (2) For the purpose of the assessment under paragraph (1), any measurements collected under sub-paragraph (a)(ii) of that paragraph for any period for which any part of a water-cooled chiller in the prescribed system is producing chilled water requiring the use of antifreeze, must be disregarded in the assessment of the energy efficiency of a prescribed system under that paragraph. [S 719/2025 wef 01/12/2025] |
(3) The information mentioned in paragraph (1)(a)(iii) and (b) comprises all of the following:| (a) | where any cooling tower of the prescribed system cools water from a source external to the prescribed system and any prescribed measuring instrument measures a parameter partially attributable to that external source — the heat gained by and heat lost from cooling water from that external source; [S 719/2025 wef 01/12/2025] | | (b) | the electrical energy and electrical power consumed by all chilled water pumps in the prescribed system in pumping chilled water through all the evaporators in the prescribed system, based on the ratio of its flowrate to the total flowrate through the pumps, if applicable; | | (c) | the electrical energy and electrical power consumed by all condenser water pumps in the prescribed system in pumping water through all the water-cooled condensers in the prescribed system, based on the ratio of its flowrate to the total flowrate through the pumps, if applicable; | | (d) | the electrical energy and electrical power consumed by all cooling towers in the prescribed system in rejecting heat from water that passes through all the water-cooled condensers in the prescribed system, based on the ratio of its heat rejected to the total heat rejected by the cooling towers, if applicable; | | (e) | the operating hours of the prescribed system; | | (f) | the refrigeration output and refrigeration energy output of the chilled water, the rate and amount of heat removal from the condenser water, and the electrical energy and electrical power consumption of the prescribed system; [S 719/2025 wef 01/12/2025] | | (g) | the energy performance of the following groups of equipment in the prescribed system:| (i) | the water-cooled chillers; | | (ii) | the chilled water pumps; | | (iii) | the condenser water pumps; | | (iv) | the cooling towers; |
| | (h) | the energy performance of the prescribed system; | | (i) | the heat balance of the prescribed system, calculated in accordance with paragraph B.2.2 of SS 591/2013. |
|
| (4) For the purposes of converting refrigeration output in refrigerant ton to kWc, the refrigeration output in unit of refrigerant ton must be multiplied by 3.517 kWc/RT. [S 972/2020 wef 01/12/2020] |
|
| Prescribed manner and period of monitoring |
7KA.—(1) For the purposes of section 26B(2)(a)(ii) of the Act, the monitoring of the energy efficiency of a prescribed system (or any part of the system) serving any business activity or premises under the operational control of a registered relevant person, must be carried out using an energy management system which is capable of —| (a) | aggregating the measurements collected by the prescribed measuring instruments, for the purpose of generating a monitoring report in the format provided at https://www.nea.gov.sg; and | | (b) | displaying all of the information listed in paragraph (2) in real time. |
(2) The information mentioned in paragraph (1)(b) is the following:| (a) | the operational status of the individual components of the prescribed system; | | (b) | the positions, in a visual representation of the prescribed system, of the instruments of the prescribed system; | | (c) | the temperature setpoints; | | (d) | the percentage system heat balance, where applicable; | | (e) | one-minute interval values of the following:| (i) | all the following measured parameters of each water-cooled chiller in the prescribed system:| (A) | the chilled water supply temperature; | | (B) | the chilled water return temperature; | | (C) | the condenser water supply temperature; | | (D) | the condenser water return temperature; | | (E) | the flowrate of the chilled water in the water-cooled chiller; | | (F) | the flowrate of the condensed water in the water-cooled chiller; |
| | (ii) | the refrigeration output and refrigeration energy output of the chilled water; | | (iii) | the rate and amount of heat removal from the condenser water; | | (iv) | the electrical energy and electrical power consumption of the prescribed system and the following groups of equipment in the prescribed system:| (A) | the water-cooled chillers; | | (B) | the chilled water pumps; | | (C) | the condenser water pumps; | | (D) | the cooling towers; |
| | (v) | the energy performance of the prescribed system and the groups of equipment in the prescribed system listed in sub-paragraph (iv). |
|
|
| (3) For the purposes of section 26B(2)(a)(ii) of the Act, the prescribed period for the monitoring of the energy efficiency of a prescribed system is any continuous period of 14 days in every calendar year, beginning with the year (called in this Part year A) in which the assessment report is submitted under regulation 7MA. [S 719/2025 wef 01/12/2025] |
|
| Minimum energy efficiency standard |
| 7L. For the purposes of section 26B(3) of the Act, the prescribed minimum energy efficiency standard specified in the third column of Part 1 of the Fifth Schedule is the prescribed minimum energy efficiency standard for the prescribed system specified in the second column of Part 1 of the Fifth Schedule, serving the premises or the business activity specified in the first column of Part 1 of the Fifth Schedule, against that minimum energy efficiency standard. [S 719/2025 wef 01/12/2025] |
| Requirements for assessment reports |
7M.—(1) [Deleted by S 719/2025 wef 01/12/2025](2) Any assessment report (whether under section 26B(2)(b)(i) or (3)(b) of the Act) on the prescribed system must include the following, where applicable:| (a) | details of the components of the prescribed system, including —| (i) | the unique identification of each component; | | (ii) | the type of each component, including whether variable frequency drives are present; | | (iii) | the installation year of each component; | | (iv) | the refrigeration capacity of each chiller at standard rating conditions in accordance with the specified AHRI Standard or when rated in accordance with the operational conditions required for the business activity; [S 719/2025 wef 01/12/2025] | | (v) | the input power to each chiller where the refrigeration output corresponds to refrigeration capacity of the chiller mentioned in sub-paragraph (iv); | | (vi) | the chilled water supply temperature setpoint of each chiller; | | (vii) | the designed difference in chilled water supply temperature and return temperature of each chiller; | | (viii) | the rated performance of each chiller at standard rating conditions in accordance with the specified AHRI Standard or when rated in accordance with the operational conditions required for the business activity; [S 719/2025 wef 01/12/2025] | | (ix) | the rated motor output power for each chilled water pump, condenser water pump and cooling tower fan; | | (x) | the pump head of each chilled water pump and condenser water pump; | | (xi) | the flowrate of each chilled water pump, condenser water pump and cooling tower; | | (xii) | the rated pump efficiency for each chilled water pump and condenser water pump; | | (xiii) | the rated fan efficiency for each cooling tower fan; | | (xiv) | the rated motor efficiency for each chilled water pump, condenser water pump and cooling tower fan; | | (xv) | an indication if the power consumption of each chilled water pump, condenser water pump and cooling tower fan is attributable only to the prescribed system; and | | (xvi) | the schematic of the prescribed system, including all components of the system; |
| | (b) | details of the prescribed measuring instruments installed, including —| (i) | the unique identification of each instrument; | | (ii) | the type of each instrument; | | (iii) | the parameter measured by each instrument; | | (iv) | the location of each instrument; | | (v) | the instrument range of each instrument; | | (vi) | the frequency of measurement taken by each instrument; | | (vii) | the end-to-end uncertainty of each measurement; | | (viii) | the last calibration date of each instrument; and | | (ix) | the location of each instrument superimposed on the schematic of the prescribed system; [S 719/2025 wef 01/12/2025] |
| | (c) | the assessment period; | | (d) | the information, documents or analyses relied upon by the qualified person in certifying the matters mentioned in regulation 7K(1)(b) and in conducting the verification in regulation 7K(1)(c); | | (e) | the reasons given to the Director-General under section 31B of the Act or regulation 7J(6) for any waiver or modification of a requirement under section 26B of the Act or in this Part, if any; | | (f) | the reasons for failing to comply with any requirement under section 26B of the Act or in this Part, if any; | | (g) | such other information or document as the Director-General may require. [S 719/2025 wef 01/12/2025] |
|
(3) The report specified in paragraph (2) must be —| (a) | endorsed by the qualified person mentioned in regulation 7K(1)(b); | | (b) | endorsed by the chief executive of the registered relevant person; [S 719/2025 wef 01/12/2025] | | (c) | submitted in the manner specified by the Director-General; and | | (d) | endorsed and submitted by an employee of the registered relevant person who is authorised by the registered relevant person for this purpose. [S 972/2020 wef 01/12/2020] [S 719/2025 wef 01/12/2025] |
|
|
| Prescribed period for submission of assessment reports |
| 7MA. Where X in regulation 7AC is a registered relevant person, X must, in relation to each prescribed system (or any part of the system) serving the premises mentioned in regulation 7G(a) or business activity mentioned in regulation 7G(b) under the operational control of X, complete an assessment mentioned in section 26B(2)(a)(i) of the Act and submit an assessment report mentioned in section 26B(2)(b)(i) of the Act in accordance with the Fourth Schedule. [S 719/2025 wef 01/12/2025] |
| Requirements for monitoring reports |
7MB.—(1) A monitoring report must be in the reporting format mentioned in regulation 7KA(1)(a).(2) The monitoring report must include the following measurements:| (a) | the total electrical energy consumed by the prescribed system; | | (b) | the total system refrigeration energy output; | | (c) | the total system heat rejection; | | (d) | the average chilled water supply temperature; | | (e) | the refrigeration energy output of the chilled water at each chilled water supply temperature; | | (f) | the average energy performance of the following groups of equipment in the prescribed system:| (i) | the water-cooled chillers; | | (ii) | the chilled water pumps; | | (iii) | the condenser water pumps; | | (iv) | the cooling towers; |
| | (g) | the average energy performance of the prescribed system; | | (h) | the operating hours of the prescribed system; | | (i) | the heat balance of the prescribed system, calculated in accordance with paragraph B.2.2 of SS 591/2013; | | (j) | any other information or document that the Director-General may require. |
|
(3) The monitoring report mentioned in paragraph (1) must be —| (a) | endorsed by the chief executive of the registered relevant person; | | (b) | submitted in the manner specified by the Director-General; and | | (c) | endorsed and submitted by an employee of the registered relevant person who is authorised by the registered relevant person for this purpose. [S 719/2025 wef 01/12/2025] |
|
|
| Prescribed period for submission of monitoring reports |
7MC.—(1) A registered relevant person must submit a monitoring report in respect of a prescribed system —| (a) | if the prescribed system is in a new building (or any part of the building) under the operational control of the registered relevant person, and —| (i) | the assessment report for the prescribed system mentioned in regulation 7M is submitted to the Director-General on or before 30 June of year A (mentioned in regulation 7KA(3)) — by 30 June of year A + 1; and | | (ii) | the assessment report for the prescribed system mentioned in regulation 7M is submitted after 30 June of year A — by 30 June of year A + 2; or |
| | (b) | if the prescribed system is in any premises (or any part of the premises) under the operational control of the registered relevant person, that do not comprise a new building — by 30 June of year A + 1. |
| (2) A registered relevant person must also submit a monitoring report by 30 June of each year subsequent to year A in paragraph (1), in relation to monitoring carried out for a continuous 14-day period in the year immediately before the year in which the report is required to be submitted under this paragraph. [S 719/2025 wef 01/12/2025] |
|
| Requirements relating to keeping of records |
7N.—(1) Records containing the following information must be kept for the purposes of section 29(1) of the Act:| (a) | all measurements mentioned in regulation 7K(1)(a) and information mentioned in regulation 7K(3); | | (b) | all calculations mentioned in regulation 7K made by the qualified person in preparing the assessment report; | | (c) | the drawings of the prescribed system plant room layout indicating details of the location of every prescribed measuring instrument and any test plug or thermowell; [S 719/2025 wef 01/12/2025] | | (d) | all schematic drawings of the prescribed system; [S 719/2025 wef 01/12/2025] | | (e) | all calibration certificates from accredited laboratories or factory calibration certificates from manufacturers for every prescribed measuring instrument; [S 719/2025 wef 01/12/2025] | | (f) | all input parameters for every prescribed measuring instrument; [S 719/2025 wef 01/12/2025] | | (g) | the technical specifications of each component of the prescribed system; | | (h) | any other information relied on in preparing the assessment report. |
| (2) For the purposes of section 29(2)(a) of the Act, the prescribed period to keep and maintain the records mentioned in paragraph (1) in relation to an assessment report is 5 years after the date the assessment report is submitted. |
| (3) Without affecting paragraph (2), the measurements mentioned in regulation 7K(1)(a) and information mentioned in regulation 7K(3) must be kept in the energy management system for a period of at least 3 years after the date the assessment report is submitted. [S 972/2020 wef 01/12/2020] |
|
|